4.4 Two quick scanning modes of function code

580 series has many function codes. To help the user for quick scanning, the frequency converter is further provided with two quick scanning modes of function code:

1) The user can select and customize at most 30 common function codes to form a function code set defined by the user; the user will determine the function parameter to be displayed by Group FE

2) The frequency converter will arrange the frequency code that is different from default value for quick scanning by the user.

For three kinds of function code scanning modes, the display code of all parameter display modes is as follows:


Parameter display mode

Display

Function parameter mode



User customized parameter mode



User modified parameter mode



Three kinds of function code display modes can be switched by QUICK key. The scanning or modification method of all function codes is the same as previous keyboard operation:

Fig. 4-4 Scanning mode of function code parameter

Therein, Function Code FP-03 is used to control user customized group and user modification parameter group.


FP-03

Default value: 11

Set value

Tens place

Ones place

Function

group display election

group display selection

Set range

0: Not displayed; 1: displayed

0: Not displayed; 1: displayed

basic function code block

The basic function code block, namely, the whole function code of frequency converter, is Level I menu after entry. Only inquiry or modification is available according to previous operation mode.



user customized function code block

The setup of user customized menu is mainly used to help the user for quick inquiry and modification of commonly-used function parameters. The parameter is displayed as “uF3.02” in the user customized menu and this form indicates function parameter F3-02. The parameter modification in the user customized menu has the same effect as the parameter modification in common programming state. It is Level II menu after entry.

The function parameter of user customized menu is from Group FE. Group FE selects function parameter and set as F0.00 which indicates no selection and totally 30 function parameters can be set; the “NULL” displayed in menu indicates that the user customized menu is null.

In initialization, 16 commonly-used parameters have been stored in the user customized menu to facilitate the user in operation:

Table 4-3 Commonly-used parameters of the user customized menu

Function code

Name

Function code

Name

F0-01

Control mode

F0-02

Command source selection

F0-03

Selection of main frequency source

F0-07

Command source selection

F0-08

Preset frequency

F0-17

Acceleration time

F0-18

Deceleration time

F3-00

V/F curve setting

F3-01

Torque boost

F4-00

DI1 terminal function selection

F4-01

DI2 terminal function selection

F4-02

DI3 terminal function selection

F5-04

DO1 output selection

F5-07

AO1 output selection

F6-00

Start mode

F6-10

Stop mode

The user can edit the user customization according to their specific demand.

the user has modified the composition of function code

Current set value is different from the default value and the function code has been modified by the user in the function code block modified by the user. This is a list generated by the frequency converter automatically to help the user quickly access the modified function code. It is Level II menu after entry.

4.5 Definition and operation of multifunctional key

The function of MF.K key can be defined by Function Code F7-01 and used to switch command source or change the rotation direction of frequency converter. See the interpretation of Function Code F7-01 for the specific setting method.

4.6 Consulting of state parameter

In stop or in running state, various state parameters can be displayed by shift key “ ” on the panel of frequency converter. Function F7-03 (operating parameter 1), F7-04 (operating parameter 2) and F7-05 (stop parameter) can select whether the parameter is displayed according to the binary digit. In stop state, 16 down state parameters in total are available to determine display or no display, respectively including:




F7-05

LED stop display parameter

Bit00: Set frequency (Hz)

Bit01: Bus voltage (V)

Bit02: DI input state

Bit03: DO output state

Bit04: AI1 voltage (V)

Bit05: AI2 voltage (V)

Bit06: AI3 voltage (V)


Bit07: Count value

Bit08: Length value

Bit09: PLC stage

Bit10: Load speed

Bit11: PID setting

Bit12:PULSE input pulse frequency



33



Switch and display the parameters selected according to key sequence.

In running state, five running state parameters, including operation frequency, set frequency, bus voltage, output voltage and output current, are displayed in default. The display of other parameters is determined by Function Code F7-03 and F7-04:




F7-03

LED running

display parameter 1



Bit00: Operation frequency

1(Hz)


Bit01: Set frequency (Hz)

Bit02: Bus voltage

Bit03: Output voltage

Bit04: Output current (A)

Bit05: Output power (kW)

Bit06: Output torque (%)

Bit07: DI input state


Bit08: DO output state

Bit09: AI1 voltage (V)

Bit10: AI2 voltage (V)

Bit11: AI3 voltage (V)

Bit12: Count value

Bit13: Length value

Bit14: Load speed display

Bit15: PID setting



1F



F7-04

LED running

display parameter 2



Bit00: PID feedback

Bit01: PLC stage

Bit02: PULSE input

frequency

Bit03: Operation frequency

2 (Hz)


Bit04: Residual running time

Bit05: Voltage before AI1

calibration

Bit06: Voltage before AI2

calibration

Bit07: Voltage before AI3

calibration


Bit08: Linear velocity

Bit09: Current power-on

time

Bit10: Current running time



Bit11: PULSE input

frequency

Bit12: Communication set

value


Bit13: Encoder feedback

speed


Bit14: Main frequency X

display (Hz)

Bit15: Auxiliary frequency

Y display (Hz)



33



If the frequency converter of which the power supply is cut off is powered on, the displayed parameter will be taken as the parameter selected before the power supply of frequency converter is off.

Switch and display the parameters selected according to the key sequence. The parameter setting mode is as follows:

For example, the user sets the parameters to be switched and displayed as: Operation frequency, bus voltage, output voltage, output current, output power, output torque, PID feedback and encoder feedback speed. The binary data shall be set according to the corresponding place of actual display data:

F7-03 is 0000 0000 0111 1101B

F7-04 is 0010 0000 0000 0001B

Converting into hexadecimal data:

F7-03 is 007DH

F7-04 is 2001H

The set value of keyboard is displayed as: F7-03 : H.1043, F7-04 : H.2001

4.7 Start and stop control of frequency converter




Download 23,63 Mb.

Do'stlaringiz bilan baham:
1   ...   26   27   28   29   30   31   32   33   ...   63




Ma'lumotlar bazasi mualliflik huquqi bilan himoyalangan ©hozir.org 2024
ma'muriyatiga murojaat qiling

kiriting | ro'yxatdan o'tish
    Bosh sahifa
юртда тантана
Боғда битган
Бугун юртда
Эшитганлар жилманглар
Эшитмадим деманглар
битган бодомлар
Yangiariq tumani
qitish marakazi
Raqamli texnologiyalar
ilishida muhokamadan
tasdiqqa tavsiya
tavsiya etilgan
iqtisodiyot kafedrasi
steiermarkischen landesregierung
asarlaringizni yuboring
o'zingizning asarlaringizni
Iltimos faqat
faqat o'zingizning
steierm rkischen
landesregierung fachabteilung
rkischen landesregierung
hamshira loyihasi
loyihasi mavsum
faolyatining oqibatlari
asosiy adabiyotlar
fakulteti ahborot
ahborot havfsizligi
havfsizligi kafedrasi
fanidan bo’yicha
fakulteti iqtisodiyot
boshqaruv fakulteti
chiqarishda boshqaruv
ishlab chiqarishda
iqtisodiyot fakultet
multiservis tarmoqlari
fanidan asosiy
Uzbek fanidan
mavzulari potok
asosidagi multiservis
'aliyyil a'ziym
billahil 'aliyyil
illaa billahil
quvvata illaa
falah' deganida
Kompyuter savodxonligi
bo’yicha mustaqil
'alal falah'
Hayya 'alal
'alas soloh
Hayya 'alas
mavsum boyicha


yuklab olish