10
|
Qk10
|
444
|
1,169
|
0,327
|
373.848
|
519,036
|
400
|
2
|
4+1
|
320+80
|
119
|
0,38-80-1UZ
0,38-320-4UZ
|
11
|
Qk11
|
309
|
0,881
|
0,327
|
171.186
|
272,22
|
245
|
1
|
3
|
245
|
27.22
|
0,38-245-3UZ
|
Σ
|
|
5613,18
|
|
|
|
5251,464
|
4515
|
|
|
|
1227,73
|
|
Sexlar buyicha to‘la hisobiy quvvatni aniqlaymiz
Sexlarning aktiv quvvatiRrs = Rr0,4 + R10 + Rro
Rrs = 5613.18 + 3823+ 519.01= 9955.19 kVt
3) Sexlarning reaktiv quvvati Qrs = Qr,04 + Qr10
Qrs = 5251,464+ 3248,3= 8499.76 kVar
Territoriyani yorituvchm hisobiy quvvat (Rud = 0,15 Vt/m)
Rot = Rud(Fter – ΣFosv)/1000
Rot = 0,15 ∙ (223100 – 42750)/1000 = 27 kVt
Kompensatsiyagacha zavodni to‘la quvvatini hisoblaymiz
Zavod buyicha aktiv quvvatRrz = Rr0,4 + Rr10 + Rro + Rot
Rrz = 5613,18+ 3823+ 519.01+ 27 = 9982.19 kVt
Zavod buyicha reaktiv quvvatQrz = Qr,04 + Qr10
Qrz = 5251,464+ 3248,3= 8499.76 kVar
Zavod buyicha to‘la quvvat
kV*A
cosφ= Rrz / Srz = 9982.19 / = 0.76
1.2.Reaktiv quvvatni kompensatsiya kilish
Sinxron dvigatellar yordamida reaktiv quvvatni kompensatsiya kilish
Ularni ortikcha qo’zg‘atish toki yordamida amalga oshiriladi, shuning uchun Un = 10 kV sinxron dvigatellarda cosφ= 1,
0,4 kV kuchlanish tomonda reaktiv quvvatni kompensatsiya kilish komplekt kondensator qurilmalar(KKK) yordamida amalga oshiriladi. Har bir rostlanish pag‘onasi KKK = 80 kVA, cosφ esa 0,95 ga teng deb olinadi. YA’ni tgφ= 0,38. Hisoblashlar natijasida KKKni tanlaymiz (masalan, KKU-0,38-xxx-xUZ seriya). Bunda kompensatsiya kilinishi shart bo‘lgan reaktiv quvvat
Qk = Rr (tgφi – tgφn) kVar
Q`k = Reaktiv quvvatni generatsiya qiluvchi KKK; Qd - bittaKKK
Q`k = KKU ∙ Qb
Zavod buyicha kompensatsiyadan quvvatlarni hisoblaymiz
Zavod buyicha aktiv quvvatR`rz = Rrz
R`rz = 9982.19 kVt
Zavod buyicha reaktiv quvvatQ`rz = Qrz – Q`k – Qr10
Q`rz = 8499.76 – 4130 – 3248,3= 1121,46 kVar
Zavod buyicha to‘la quvvat
kVA
Pasaytiruvchi transformatorlarda quvvatlar isrofi
∆RT = 0,02 ∙ Srs
∆QT = 0,1 ∙ Srs
∆RT = 0,02 ∙ = 201 kVt
∆QT = 0,1 ∙ = 1004.5 kVar
Transformatorlardagi quvvatlar isrofini hisobga olib kompensatsiyadan keyingi zavod buyicha hisobiy quvvat
10402.5kVA
Quvvat koeffitsienti
cos`φ= R`rz / S`rz = / 10402.5= 0.97
Sexlar va zavod bo‘yicha quvvatlarni yig‘ish.
5-jadval
t/r
|
Sexlarni nomlanishi
|
Rust
kVt
|
kspr
|
cosφ
|
tgφ
|
Rr
kVt
|
Qr
kVar
|
Sr
kVA
|
Rud. osv
Vt/m2
|
Ks
|
Rro
kVt
|
Q`k
kVar
|
S`k
kVA
|
1
|
Mexanika sexi №1
|
2200
|
0,3
|
0,6
|
1,33
|
660
|
880
|
1100
|
14,3
|
0,95
|
62.15
|
145
|
726,76
|
2
|
Kuyish sexi №1
|
1100
|
0,8
|
0,85
|
0,619
|
880
|
544,72
|
1034,949
|
12.4
|
0,95
|
97.77
|
54.72
|
979,29
|
3
|
Kuyish sexi№2
|
990
|
0,8
|
0,85
|
0,619
|
792
|
490,248
|
931,4543
|
12.4
|
0,95
|
40
|
245.248
|
867,3
|
4
|
Temirchilik sexi
|
1380
|
0,3
|
0,6
|
1,33
|
414
|
550,62
|
688,8965
|
14.3
|
0,95
|
28.5
|
60.6
|
443,9
|
5
|
Mexanika sexi №2
|
2700
|
0,3
|
0,6
|
1,33
|
810
|
1080
|
1350
|
14.3
|
0.95
|
16.3
|
120
|
834,9
|
6
|
Termik sexi №1 0,4 kv
Termik sexi №2 10 kv
|
1800
1980
|
0,75
|
0,85
0.85
|
0,619
|
1350
1485
|
835,65
1512,8
|
635
2120
|
15.6
|
0.95
|
40
|
195,64
-
|
1411,4
1485
|
7
|
Komp.sexi №1 0.4kv
Komp.sexi №1 10kv
|
520
3340
|
0,7
|
0,8
0.8
|
0,75
|
364
2338
|
273
1753,5
|
455
2922
|
9.1
|
0,95
|
23.3
|
113
-
|
403,8
2338
|
8
|
Nasos sexi
|
460
|
0,75
|
0,8
|
0,75
|
345
|
258,75
|
431,25
|
12
|
0,95
|
32.49
|
98.7
|
390,1
|
9
|
Kotel sexi
|
178
|
0,31
|
0,75
|
0,881
|
55,18
|
48,61
|
73,5375
|
15,6
|
0.85
|
12
|
48,61
|
83
|
10
|
Mex. Ta’mirlash sexi.
|
1200
|
0,37
|
0,65
|
1,169
|
444
|
519,036
|
683,0332
|
15
|
0,95
|
120.4
|
119
|
576,8
|
11
|
Zavod boshqarma
|
515
|
0,6
|
0,75
|
0,881
|
309
|
272,22
|
411,8067
|
9,2
|
0,9
|
46.1
|
27.22
|
356,1
|
|
Jami:
|
|
|
0,61
|
1,29
|
9436,18
|
8499,4
|
12835,8
|
|
|
519.01
|
1227,73
|
10071,75
|
Izoh: S`k - zavodni territoriyasini yoritish quvvati va transformatorning aktiv quvvatini isrofini hisobga olmagan holdagi tula quvvatidir
2. Elektr yuklamalar markazini aniqlash(EYUM) va elektr yuklamalarning kartogrammasini kurish.
Do'stlaringiz bilan baham: |