Cosφ
|
φ
|
tgφ
|
O‘zgarmas aktiv tok va quvvatda (100 foiz)
|
Tok bilan ajraladigan issiqlik oqibatida quvvat yo‘qotishlarining o‘sishi
|
toklarning nisbati
|
reaktiv
|
to‘liq
|
i sinφ
|
i
|
aktiv tok foizi
|
1.0
|
-
|
-
|
0
|
100
|
1
|
0.95
|
18.20
|
0.33
|
33
|
105.3
|
1.11
|
0.9
|
25.86
|
0.48
|
48.4
|
111.1
|
1.23
|
0.85
|
31.80
|
0.62
|
61.9
|
117.6
|
1.38
|
0.8
|
36.89
|
0.75
|
75
|
125
|
1.56
|
0.75
|
41.43
|
0.88
|
88.1
|
133.3
|
1.78
|
0.7
|
45.60
|
1.02
|
102.1
|
142.9
|
2.01
|
0.65
|
49.48
|
1.17
|
116.9
|
153.8
|
2.37
|
0.6
|
53.16
|
1.33
|
133.3
|
166.7
|
2.78
|
0.55
|
56.66
|
1.52
|
151.8
|
181.8
|
3.31
|
0.5
|
60.03
|
1.73
|
173.2
|
200
|
4
|
0.45
|
63.29
|
1.98
|
198.4
|
222.2
|
4.94
|
0.4
|
66.46
|
2.29
|
229.1
|
250
|
6.25
|
0.35
|
69.55
|
2.68
|
267.6
|
285.7
|
8.16
|
0.3
|
72.58
|
3.18
|
317.9
|
333.3
|
11.11
|
0.25
|
75.56
|
3.87
|
387.3
|
400
|
16
|
0.2
|
78.50
|
4.90
|
490
|
500
|
25
|
0.15
|
81.41
|
6.59
|
659
|
667
|
44.4
|
0.1
|
84.30
|
9.95
|
995
|
1000
|
100
|
2-jadval
Aktiv va reaktiv toklarning to‘liq quvvatni o‘zgarmas kattaligida cosφ ga bog‘liq holda nisbatlari
Cosφ
|
φ
|
tgφ
|
Doimiy to‘liq quvvatda toklarning nisbati (100 foiz)
|
Aktiv quvvatning o‘zgarishi
|
Tok bilan ajraladigan issiqlik oqibatida quvvat yo‘qotishlarining o‘sishi
|
aktiv
|
reaktiv
|
I cosφ
|
I sinφ
|
to‘liq tok foizi
|
foiz
|
1.0
|
-
|
-
|
100
|
0
|
100
|
1
|
0.95
|
18.20
|
0.33
|
95
|
31.2
|
95
|
1.05
|
0.9
|
25.86
|
0.48
|
90
|
43.6
|
90
|
1.11
|
0.85
|
31.80
|
0.62
|
85
|
52.7
|
85
|
1.18
|
0.8
|
36.89
|
0.75
|
80
|
60
|
80
|
1.25
|
0.75
|
41.43
|
0.88
|
75
|
66.1
|
75
|
1.33
|
0.7
|
45.60
|
1.02
|
70
|
71.4
|
70
|
1.43
|
0.65
|
49.48
|
1.17
|
65
|
76
|
65
|
1.51
|
0.6
|
53.16
|
1.33
|
60
|
80
|
60
|
1.67
|
0.55
|
56.66
|
1.52
|
55
|
83.5
|
55
|
1.82
|
0.5
|
60.03
|
1.73
|
50
|
86.6
|
50
|
2
|
0.45
|
63.29
|
1.98
|
45
|
89.3
|
45
|
2.22
|
0.4
|
66.46
|
2.29
|
40
|
91.7
|
40
|
2.5
|
0.35
|
69.55
|
2.68
|
35
|
93.7
|
35
|
2.86
|
0.3
|
72.58
|
3.18
|
30
|
95.4
|
30
|
3.33
|
0.25
|
75.56
|
3.87
|
25
|
96.8
|
25
|
4
|
0.2
|
78.50
|
4.90
|
20
|
98
|
20
|
5
|
0.15
|
81.41
|
6.59��
|
15
|
98.9
|
15
|
6.67
|
0.1
|
84.30
|
9.95
|
10
|
99.5
|
10
|
10
|
3-jadval
“Iste’molchi”
tomonidan kelishilgan, iste’mol qilinadigan reaktiv quvvat va energiyaning iqtisodiy qiymatlari
Yil, Oy
|
Maksimal yuklamali soatlarda energiya tizimidan bir oyda iste’mol qilinadigan reaktiv energiyaning iqtisodiy qiymati (kVAr*soat)
|
Maksimal yuklamali soatlarda energiya tizimidan bir oyda iste’mol qilinadigan reaktiv quvvatning iqtisodiy qiymati (kVAr)
|
Energiya tizimining maksimal yuklamali soatlari
|
Energiya tizimining minimal yuklamali soatlari
|
Yanvar
| | | | |
Fevral
| | | | |
Mart
| | | | |
Aprel
| | | | |
May
| | | | |
Iyun
| | | | |
Iyul
| | | | |
Avgust
| | | | |
Sentyabr
| | | | |
Oktyabr
| | | | |
Noyabr
| | | | |
Dekabr
| | | | |
4-jadval
Kompensatsiyalovchi qurilmalarni ishlash rejimlari. Kompensatsiyalovchi qurilmalarning o‘rnatilgan quvvati
Oldingi tahrirga qarang.
№
|
Kompensatsiyalovchi qurilmaning turi
|
Quvvat
|
Ulanish vaqti
|
Qiymati
|
ertalab
|
kechqurun
|
1.
|
Kondensator qurilmalari, kVAr 1000 V gacha va undan yuqori, shu jumladan:
| | | | |
1.1. Avtomatik boshqariladigan: 1000 V gacha va undan yuqori
| | | | |
1.2. Qo‘lda boshqariladigan: 1000 V gacha va undan yuqori
| | | | |
2.
|
Sinxron dvigatellar (SD), kW
| | | | |
3.
|
Mavjud reaktiv quvvat SD, kVAr (belgilangan quvvatning 30 foizi SD, kVt)
| | | | |
4.
|
Jami (1 p. + 3 p.) kVAr;
1000 V gacha va undan yuqori
| | | | |
(4-jadval O‘zbekiston Respublikasi Elektr energetikada nazorat bo‘yicha davlat inspeksiyasi boshlig‘ining 2014-yil 3-apreldagi 4-sonli buyrug‘i (ro‘yxat raqami 1864-1, 10.04.2014-y.) tahririda — O‘R QHT, 2014-y., 15-son, 175-modda)
Oldingi tahrirga qarang.
4-§. Quvvat koeffitsiyentini pasayishi oqibatida elektr energiyasini qo‘shimcha texnologik yo‘qotishlarini hisoblash
18. Hisob-kitoblarni amalga oshirish uchun kerak bo‘ladigan birlamchi ma’lumotlar:
a) hisob davrida iste’molchiga amalda yetkazib berilgan aktiv va reaktiv elektr energiyasi miqdori W
a, W
r;
b) elektr ta’minoti shartnomasida belgilangan quvvat koeffitsiyenti (sos φ
shart);
v) Elektr energiyasini elektr tarmoqlari bo‘ylab uzatish va taqsimlashda texnologik yo‘qotishlarning normativlarini hisoblash tartibi to‘g‘risidagi yo‘riqnomaga (ro‘yxat raqami 2871, 2017-yil 31-mart) muvofiq hisoblangan iste’molchi ulangan elektr tarmoqlar bo‘ylab elektr energiyasini uzatish va taqsimlashda uning texnologik yo‘qotishlarning normativi (∆
W Norm.ETY, %).
Hisob davrida iste’molchiga amalda yetkazib berilgan aktiv va reaktiv elektr energiyasi
miqdoridan kelib chiqib, amaldagi quvvat koeffitsiyenti quyidagi formula bo‘yicha hisoblanadi:
Hisob davrida elektr energiyasini iste’molchiga yetkazib berishda iste’molchi ulangan tarmoqlarda sodir bo‘ladigan uning texnologik yo‘qotishlarining absolyut miqdori (∆
W Norm.ETY)quyidagi formula bo‘yicha aniqlanadi:
Bunda,
Wa hisob davrida iste’molchiga yetkazib berilgan aktiv elektr energiyasi miqdori.
Mazkur Metodikaning 17-bandiga asosan quvvat koeffitsiyenti kamayishi oqibatida elektr energiyasini elektr tarmoqlari bo‘ylab uzatishda uning texnologik yo‘qotishlari marta ortishi inobatga olinsa, hisob davrida iste’molchiga elektr energiyasi yetkazib berish uchun elektr tarmoqlardagi elektr energiyasi yo‘qotishlarining:
elektr ta’minoti shartnomasi bilan cheklangan miqdori:
amaldagi miqdori:
Iste’molchida quvvat koeffitsiyenti elektr ta’minoti shartnomasida belgilangandan pasayishi oqibatida elektr tarmoqlarda sodir bo‘ladigan qo‘shimcha elektr energiyasi yo‘qotishlari quyidagi formula bilan aniqlanadi:
(4-§ Elektr energetikada nazorat bo‘yicha davlat inspeksiyasi boshlig‘ining 2018-yil 26-iyuldagi 10-son buyrug‘iga (ro‘yxat raqami 1864-2, 05.09.2018-y.) asosan kiritilgan — Qonun hujjatlari ma’lumotlari
milliy bazasi, 05.09.2018-y., 10/18/1864-2/1834-son)
(O‘zbekiston Respublikasi qonun hujjatlari to‘plami, 2008-y., 40-41-son, 419-modda; 2014-y., 15-son, 175-modda; Qonun hujjatlari ma’lumotlari milliy bazasi, 05.09.2018-y., 10/18/1864-2/1834-son)