Inverter unit
protection
|
Err01
|
1. Short circuit for frequency converter output circuit
2. Too long wiring between motor and frequency converter
3. Too hot module
4. Loose internal wiring for frequency converter
5. Abnormal main control panel
6. Abnormal drive board
7. Abnormal inverse module
|
1. Troubleshoot the external failure
2. Install electric reactor or output filter
3. Inspect if the air channel is blocked, and if fan functions normally and then troubleshoot the existing problems
4. Properly plug in all the connecting lines;
5. Seek technical support;
6. Seek technical support;
7. Seek technical support;
|
Overcurrent
during
acceleration
|
Err02
|
1. Grounding or short circuit exist in the output circuit of frequency converter
2. The control mode is vector and parameter identification is not conducted
3. Too short acceleration time
4 Improper manual torque lifting or V/F curve
5 Relatively low voltage
6. Start the motor which are rotating
7. Sudden load in the acceleration process
8. Relatively small model selection for frequency converter
|
1. Troubleshoot the external failure
2. Conduct the motor parameter identification
3. Increase the acceleration time
4. Modify manual lifting torque or V/F curve
5. Adjust the voltage to the normal range
6. Select the rotating tracing start or restart after the motor stops
7. Cancel sudden load
8. Choose frequency converter with bigger power level
|
Overcurrent
during
deceleration
|
Err03
|
1 Grounding or short circuit exit in the output circuit of frequency converter
2. The control mode is vector and parameter identification is not conducted
3. Too short deceleration time
4. Relatively low voltage
5. Sudden load in the deceleration process
6. No installing of brake unit or brake resistance
|
1. Troubleshoot the external failure
2. Conduct the motor parameter identification
3. Increase deceleration time
4. Adjust the voltage to the normal range
5. Cancel sudden load
6. Install brake unit and resistance
|
Overcurrent at constant speed
|
Err04
|
1. Grounding or short circuit exit in the output circuit of frequency converter
2. The control mode is vector and parameter identification is not conducted
3. Relatively low voltage
4. Sudden load exist in the running
5. Relatively small model selection for
|
1. Troubleshoot external failure
2. Conduct the motor parameter identification
3. Adjust the voltage to the normal range
4. Cancel sudden load
5. Choose frequency converter with higher power level
|
Overvoltage
during
acceleration
|
Err05
|
1. Relatively high input voltage
2. External force dragging motor running exist in the acceleration process
3. Too short acceleration time
4. No installing of brake unit and brake resistance
|
1. Adjust the voltage to the normal range
2. Cancel the external force or install brake resistance
3. Increase acceleration time
4. Install brake unit and resistance
|
Overvoltage
during
deceleration
|
Err06
|
1. Relatively high input pressure
2. The external force dragging motor running exists in the deceleration process
3. Too short deceleration time
4. No installing brake unit and brake resistance
|
1. Adjust the voltage to the normal range
2. Cancel the external force or install brake resistance
3. Increase deceleration time
4. Install brake unit and resistance
|
Overvoltage at constant speed
|
Err07
|
1. Relatively high input pressure
2. The external force dragging motor running exists in running
|
1. Adjust the voltage to the normal range
2. Cancel the external force or install brake resistance
|
Control power
supply fault
|
Err08
|
1. The input pressure is not within the range stipulated by standard
|
1. Adjust the voltage to the range required by standard
|
Undervoltage
|
Err09
|
1. Momentary power off
2. The terminal voltage of frequency converter is not within the range required by standard
3. Abnormal Bus voltage
4. Abnormal rectifier bridge and buffer resistance
5. Abnormal drive board
6. Abnormal control panel
|
1. Reset failure
2. Adjust the voltage to the normal range
3. Seek technical support
4. Seek technical support
5. Seek technical support
6. Seek technical support
|
AC drive overload
|
Err10
|
1. Whether the load is too heavy or the motor stalling happens
2. Relatively small model selection for frequency converter
|
1. Decrease the load and inspect the motor and machinery situations
2. Choose the frequency converter with higher power level
|
Motor overload
|
Err11
|
1. Whether the setting of motor protection parameter F9-01 is appropriate
2. Whether the load is too heavy or motor stalling happens
3. Relatively small model selection for frequency converter
|
1. Correctly set the parameter
2. Decrease the load and inspect the motor and machinery situation
3. Choose the frequency converter with higher power level
|
Power input
phase loss
|
Err12
|
1. Abnormal three-phase input power
2. Abnormal drive board
3. Abnormal lightning protection plate
4. Abnormal main control panel
|
1. Inspect and troubleshoot the existing problems in the external lines
2. Seek technical support
3. Seek technical support
4. Seek technical support
|
Power output
phase loss
|
Err13
|
1. Abnormal wiring from frequency converter to motor
2. Unbalanced frequency converter three-phase when the motor is running
3. Abnormal drive board
4. Abnormal module
|
1. Troubleshoot external failure
2. Inspect whether motor three-phase winding is normal and troubleshoot the failure
3. Seek technical support
4. Seek technical support
|
Module overheat
|
Err14
|
1. Too high environment temperature
2. Air channel blocks
3. Fan damages
4. Module thermistor damages
5. Inverse module damages
|
1. Reduce environment temperature
2. Clear air channel
3. Replace fan
4. Replace thermistor
5. Replace inverse module
|
External
equipment fault
|
Err15
|
1. Input the signal of external failure through multifunctional terminal DI
2. Input the signal of external failure through virtual IO function
|
1. Reset running
2. Reset running
|
Communication fault
|
Err16
|
1. Upper computer functions abnormally
2. Abnormal communication line
3. Incorrect setting for communication expansion card F0-28
3. Incorrect setting for communication parameter Group FD
|
1. Inspect the upper computer wiring
2. Inspect communication connecting line
3. Correctly set the communication expansion card type
4. Correctly set the communication parameter
|
Contactor fault
|
Err17
|
1. The drive board and power source are abnormal
2. Abnormal contactor
|
1. Replace drive board or power panel
2. Replace the contactor
|
Current detection
fault
|
Err18
|
1. Inspect Hall device is abnormal
2. Abnormal drive board
|
1. Replace Hall device
3. Replace drive board
|
Motor auto-tuning
fault
|
Err19
|
1. The motor parameter is not set as per the name board
2. Time-out for parameter identification process
|
1. Correctly set the motor parameter as per the name board
2. Inspect the down-lead from frequency converter to motor
|
Encoder fault
|
Err20
|
1. Encoder model is not matching
2. Encoder wiring error
3. Encoder manages
4. Abnormal PG card
|
1. Correctly set the encoder type as per the actual situation
2. Troubleshoot line failure
3. Replace encoder
4. Replace PG card
|
EEPROM read-
write fault
|
Err21
|
1. EEPROM chip damages
|
1. Replace main control panel
|
AC drive
hardware fault
|
Err22
|
1. There is overpressure
2. There is overcurrent
|
1. Handling as per overpressure failure
2. Handling as per overcurrent failure
|
Short circuit to ground
|
Err23
|
1. Motor short circuit to earth
|
1. Replace cable or motor
|
Accumulative
running ime reached
|
Err26
|
1. The accumulated running time reaches up to the set value
|
1. Use parameter initialization function to clear the record information
|
User-defined fault 1
|
Err27
|
1. Input the signal of user-defined Failure 1 through multifunctional terminal DI
2. Input the signal of user-defined Failure 1 through virtual IO function
|
1. Reset running
2. Reset running
|
User-defined fault 2
|
Err28
|
1. Input the signal of user-defined Failure 2 through multifunctional terminal DI
2. Input the signal of user-defined Failure 2 through virtual IO function
|
1. Reset operation
2. Reset running
|
Accumulative
power-on time reached
|
Err29
|
1. The accumulated power-on time reaches to the set value
|
1. Use parameter initialization function to clear the record information
|
Load becoming 0
|
Err30
|
1. The running current for frequency converter is lower than F9-64
|
1. Confirm whether the load is disconnected or the parameter setting of F9-64 and F9-65 meets the real running conditions
|
PID feedback lost during running
|
Err31
|
1. The PID feedback is lower than the set value of FA-26
|
1. Inspect PID feedback signal or set FA-26 as an appropriate value
|
Waveband current limit failure
|
Err40
|
1. Whether the load is too heavy or motor stalling happens
2. Too small model selection for frequency converter
|
1. Reduce the load and inspect the motor and machinery conditions
2. Select the frequency converter with higher power level
|
Motor switchover
fault during
running
|
Err41
|
1. Change the current motor selection through terminal when the frequency converter is running
|
1. Conduct the operation of motor switching after the frequency converter stops
|
Too large speed
deviation
|
Err42
|
1. Incorrect parameter setting for encoder
2. Parameter identification is not conducted
3. Too large speed deviation, and the detecting parameter F9-69 and F9-70 are not reasonably set
|
1. Correctly set the encoder parameter
2. Conduct the motor parameter identification
3. Reasonably set the detecting parameter based on the actual conditions
|
Motor over-speed
|
Err43
|
1. Incorrect parameter setting for encoder
2. Parameter identification is not conducted
3. The motor overspeed detecting parameter F9-67 and F9-68 are not unreasonably set
|
1. Correctly set the encoder parameter
2. Conduct motor parameter identification
3. Reasonably set the detecting parameter based on actual situation
|
Motor overheat
|
Err45
|
1. Loose temperature sensor wiring
2. Motor temperature is too high
|
1. Inspect temperature sensor wiring and troubleshoot the failure
2. Reduce carrier frequency or adopt other heat emission measures to make thermal management to the motor
|
Initial position
fault
|
Err51
|
1. Too large deviation between the motor parameter and the reality
|
1. Reconfirm whether the motor parameter is correct, and focus on whether the rated current is set too small
|