Kabel liniyalarni tanlash.
0,4 kV uchun alyuminiy tomirli uch fazali ASB, AOSB markali turtta tomirli kabel tanlaymiz
10 kV kuchlanish uchun uch fazali kabel AASHV ni tanlaymiz.
Kabelni yotqizishni transheyada bajaramiz.
KTP-1:
GPP dan KTP-1gacha
S=726+356.1=1082.1 kVA, Un=10 kV, L= 285 m = 0,285km
a) Hisobiy tok
Ip = 1082.1/(2 . 1,73 . 10)=31.2 A
b) Avariya rejimidagi tok
Ia = 1082.1/(1,73 . 10)=62.5 A
v) Kabelni ko‘ndalang kesim yuzasi , bunda je = 1,2 A/mm2
F=31.2 /1,2=26 mm2
g) Kabel transheyada 2xAASHv (3x25) tanlanadi
Id.d=90 A; ΔR=40 kVt/km ; K=31.35 mln. so‘m /km
d) Avariya rejimida Id.d> Ia = 90 > 62.5 – etarli
e) YUklama koeffitsienti
K3=31.2/90=0.34
j) Kabelni narxi K`=K . L . n
K`=31.35 . 0.285 . 2 = 17.18 mln. so‘m
z) Energiya isrofi
ΔW=40 . 0,342. 2 . 0.285=2.63 kVt
k) Bir yil uchun elektr energiya isrofi narxi
UPE=2.63 .180100=0.47 mln. so‘m / yil
KTP-1 danRU1 gacha
S=356.1kVA, Un=0,4 kV, L= 15 m = 0,015 km
a) Hisobiy tok
Ip = 356.1/(4 . 1,73 . 0,4)=128.6 A
b) Avariya rejimidagi tok
Ia = 356.1/(2 . 1,73 . 0,4)=257.2 A
v) Kabelni ko‘ndalang kesim yuzasi , gde je = 1,2 A/mm2
F=128.6 /1,2 .2 =53.6mm2
g) Kabelni yotkizishni transheyada bajaramiz 4xASB (3x95+1x50)
Id.d=2x240 A; ΔR=85 kVt/km; K=36.5 mln. so‘m /km
d) Avariya rejimida 1,3 .Id.d> Ia = 624 < 514.4– etarli
e) YUklama koeffitsienti
K3=257.2 /480=0.53
j) Kabelni narxi K`=K . L . n
K`=36.5 . 0,015 . 4 = 2.19 mln. so‘m
z) Quvvat isrofi
ΔW=85 . 0,532. 4 . 0,015=1.43 kVt
k) Bir yil uchun elektr energiya isrofi narxi
UPE=1.43 . 180100=0.258 mln. so‘m / yil
KTP-2:
GPP dan KTP-2gacha
S=979.29+443.9+83+390.1=1896.29 kVA, Un=10 kV, L= 170 m = 0,17 km
a) Ip = 1896.29/(2 . 1,73 . 10)=54.8 A
b) Ia = 1896.29/(1,73 . 10)=109.6 A
v) Kabelni ko‘ndalang kesim yuzasi F=54.8 /1,2=45.6mm2
g) Kabelni yotqizishni transheyada bajaramiz 2xAASHv (3x50)
Id.d=140 A; ΔR=44 kVt/km; K=1,61 mln. so‘m /km
d) Avariya rejimida Id.d> Ia = 140 > 109,6 – etarli
e) K3=54,8 /140=0,39
j) K`=1,61 . 0,17 . 2 = 0,54 mln. so‘m
z) ΔW=44 . 0,392. 2 . 0,17=2,27 kVt
k) UPE=2,27. 180100=0,4 mln. so‘m / yil
KTP-2 dan RU2 gacha
S=443.9kVA, Un=0,4 kV, L= 65 m = 0,065 km
a) Ip = 443.98/(4 . 1,73 . 0,4)=160.3 A
b) Ia = 443.9/(2 . 1,73 . 0,4)=320.7 A
v) Kabelni ko‘ndalang kesim yuzasi F=160.3 /1,2 =133.58mm2
g) Kabelni yotqizishni transheyada bajaramiz 4xASB (3x120+1x70)
Id.d=2x305 A; ΔR=88 kVt/km; K = 54 mln. so‘m /km
d) Avariya rejimida 1,3 .Id.d> Ia = 793 > 641.4 – etarli
e) K3=320.7/610=0,52
j) K`=54 . 0,065 . 4 = 14,04 mln.so‘m
z) ΔW=88 . 0,522. 4 . 0,065=6,18 kVt
k) UPE=6,18 . 180100=1,11 mln. so‘m / yil
KTP-2 dan RU3 gacha
S=83 kVA, Un=0,4 kV, L= 105 m = 0,105 km
a) Ip = 83/(2 . 1,73 . 0,4)=60 A
b) Ia = 83/( 1,73 . 0,4)=120A
v) Kabelni ko‘ndalang kesim yuzasi F=60 /1,2 =50 mm2
g) Kabelni yotqizishni transheyada bajaramiz 4xASB (3x50+1x25)
Id.d=165 A; ΔR=77 kVt/km; K = 23,5 mln. so‘m /km
d) Avariya rejimida 1,3 .Id.d> Ia = 214,5 > 120 – etarli
e) K3=60/214,5=0,28
j) K`=77 . 0,105 . 4 = 32,34 mln.so‘m
z) ΔW=77 . 0,282. 4 . 0,105=2,53 kVt
k) UPE=2,53 . 180100=0,455 mln. so‘m / yil
KTP-2 dan RU4 gacha
S=390,1 kVA, Un=0,4 kV, L= 140 m = 0,140 km
a) Ip = 390,1/(4 . 1,73 . 0,4)=141 A
b) Ia = 390,1/(2 . 1,73 . 0,4)=282A
v) Kabelni ko‘ndalang kesim yuzasi F=141 /1,2 =117,5 mm2
g) Kabelni yotqizishni transheyada bajaramiz 4xASB (3x120+1x70)
Id.d=2x305 A; ΔR=88 kVt/km; K = 54 mln. so‘m /km
d) Avariya rejimida 1,3 .Id.d> Ia = 793 > 564 – etarli
e) K3=141/305=0,46
j) K`=54 . 0,14 . 4 = 49,28 mln.so‘m
z) ΔW=88 . 0,462. 4 . 0,14=2,53 kVt
k) UPE=2,53 . 180100=0,455 mln. so‘m / yil
KTP-3:
GPP dan KTP -3gacha
S=834.9+403.8=1238.7 kVA, Un=10 kV, L= 25 m = 0,025 km
a) Ip = 1238.7 /(2 . 1,73 . 10)=35.8 A
b) Ia = 3344,2 /(1,73 . 10)=71.6 A
v) Kabelni ko‘ndalang kesim yuzasi F=35.8/1,2=30 mm2
g) Kabelni yotqizishni transheyada bajaramiz 2xAASHv (3x35)
Id.d=2*115 A; ΔR=42 kVt/km; K=36 mln. so‘m / km
d) Avariya rejimida Id.d> Ia = 115> 71.6 – etarli
e) K3=35.8/115=0,31
j) K`=36 . 0,025 . 4 = 3.6 mln.so‘m
z) ΔW=42 . 0,312. 4 . 0,025=0.4 kVt
k) UPE=0.4 . 180100=0.72 mln. so‘m / yil
Korxona elektr ta’minotining bir chiziqli prinsipial elektr sxemasi
ТП-1
2хТМ-400/10
ТП-3
2хАСБ-3х50
2хАСБ-3х50
Do'stlaringiz bilan baham: |