1-amaliy mashg’ulot
Qisqa tutashuv toklarini nomli va nisbiy birliklarda aniqlash.
II. I. Almashtirish sxemalarini tuzish va qisqa tutashish toklarni xisoblash.
Parametrlarni xisoblash uchun beriluvchi (ma’lumotlarni) qiymatlarni ma’lumotnomalardan olamiz:
a) havo va kabel liniyalari:
U=35 kB
|
|
|
AC-50
|
r0=0.592 Om/km
|
X0=0.445 Om/km
|
AC-35
|
r0=0,773 Om/km
|
X0=0,433 Om/km
|
U=10 kB
|
|
|
AABv-35
|
r0=0,89 Om/km
|
X0=0,095 Om/km
|
AAVv-25
|
r0=1,24 Om/km
|
X0=0,099 Om/km
|
b) transformatorlar:
TDN – 10000/110
|
|
Sn=10 MVA
|
R k.t =60 kVt
|
Uyu=115 kV
|
U k = 10,5 %
|
Up=35 kV
|
I.xX 1,78 %
|
|
|
TMN – 4000 kVA
|
|
Uyu=35 kV
|
R k.t =33,5 kVt
|
Up=11 kV
|
U k = 7,5 %
|
|
I xx 1,5 %
|
TMN – 1600/35
|
|
Sn=1600 MVA
|
R k.t =18 kVt
|
Uyu=35 kV
|
U k = 6,5 %
|
Up=0,4 kV
|
|
Liniya va transformatorlarning qarshiliklarini xisoblashni nisbiy birlikda olib boramiz. Buning uchun bazisli shartlarini qabul qilamiz:
Sb = S k. t = 400 MVA
UbI = 115 kV, UbII = 37 kV, UbIII = 10,5 kV
SHunda liniya:
L 1 (L 2) uchun
rb l1(2) = r0*l* = 0,592*10* = 1,73
Xb l1(2) = X0* l * = 0,445*10* = 1,3
Z l1(2) = 1,73 + j1.3 /Z l1(2)/ = 2.164
Xuddi shuningdek,
L 3 uchun
rb l(3) = r0* l * = 0,773*8* = 1,81
Xb l(3) = X0* l * = 0,443*8* = 1,01
Z l (3) = 1,81 + j1,012
L 4 (L5) uchun
rb l(4) = r0* l * = 0,89*2,2* = 7,1
Xb l(4) = X0* l * = 0,443*8* = 0,758
Z l4 (5) = 7,1 + j0,758
L 6 uchun
rb l(6) = r0* l * = 1,24*1,3* = 5,849
Xb l(6) = X0* l * = 0,099*1,3* = 0,467
Z l (6) = 5,849 + j 0,467
2-amaliy mashg’ulot
Kuchlanishi 6-10 kV li liniyalarni ximoyasini xisoblash
Transformatorlar uchun qarshiliklar quyidagicha aniqlanadi:
T 1 (T 2) uchun
Ua T1 = *100% = = 0,6%
U r T1 = = = 10,48%
rb T1 = * = * = 0,24
Xb T1 = * = * = 4,192
Z T1(T2) = 0,24 + j 4,192
Xuddi shuningdek,
T 3 uchun aniqlaymiz
Ua T3 = = 0,84%
U r T3 = = 7,45%
rb T3 = * = 0,84
Xb T3 = * = 7,45
Z T3 = 0,84 + j 7,45
Transformator T 4 uchun
Ua T4 = = 1,125%
U r T4 = = 6,4%
rb T4 = * = 2,813
Xb T4 = * = 16
Z T4 = 2,813 + j 16
3-amaliy mashg’ulot
Kuchlanishi 6-10 kV li kabel liniyalarni ximoyasini xisoblash
Elektr prinsipial sxemaga mos ekvivalent almashtirish sxemasini tuzib, taqsimlash qurilmalari shinalarida qabul qilingan va xisoblanishi shart bulgan K1 – K9 nuqtalarda qisqa tutashish toklarini belgilaymiz. (2-rasm)
Elektr ta’minoti sistemasining maksimal va minimal ish rejimda qisqa tutashish toklarining qiymatini aniqlaymiz.
T1 va T2 transformatorlar parallel ishlaganda maksimal qisqa tutashish toklari xosil buladigan rejim xisoblanadi. (2-rasm) K1 nuqta uchun S = 500 MVA qabul qilingan.
Minimal ish rejimidagi qisqa tutashish toki bitta transformator ishlaganda xosil buladigan ta’minlovchi podstansiya yuqori kuchlanish tomonidagi minimal Tula quvvat S k. t. k. = 400 MVA.
a) sistemaning maksimal ish rejimida (T1 va T2 parallel ishlaydi, S k. t. maks. = 500 MVA)
Sistema qarshiligini quyidagicha xisoblaymiz:
Xsist = = = 0,8 va Zc = j 0.8
Manba berilgan joyda qisqa tutashish nuqtasigacha bulgan qarshiliklar yigindisi:
Z e = Zc = j 0.8
Qisqa tutashish nuqtasida bazis kuchlanishdagi tok quyidagi formula yordamida aniqlanadi:
I k1 = = = 2510 A
K-2 nuqta ( 2 ta transformator ishlaganda)
ZE2 = ZE1 + ZT1/2 = j 0.8 + 0.12 + j 2.096 = 0.12 + j 2.896 = /2.898/
I k2 = = = 2154 A
K-3 nuqta
ZE3 = ZE2 + ZL1/2 = 0.12 + j 2.898 + 0,863 + j 0.65 = 0.983 +j 3.546 = /3.68/
I k3 = = = 1696 A
K – 4 nuqta
ZE4 = ZE3 + ZL3 = 0.983 + j 3.546 + 1.81 + j 1.012 = 2.793 + j 4.566 = /5.352/
I k4 = = = 1166 A
K – 5 nuqta
ZE5 = ZE3 + ZL4 = 2.793 + j 4.566 + 2.813 + j 16 = 5.606 + j 20. 566 = /21.316/
I k5 = = = 27085 A
K – 6 nuqta
ZE6 = ZE3 + ZL3 = 0.983 + j 3.546 + 0.84 + j 7.45 = 1.823 + j 10.996 = /11.146/
I k6 = = = 1973 A
K – 7(8) nuqta
Z E7 (8) = ZE6 + Z L4 (5) = 1.823 + j 10.996 + 7.1 + j 0.758 = 8.923 + j 11.754 = /14.757/
I k7 (8) = = = 1490 A
K – 9 nuqta
Z E9= ZE8 + Z L6= 8.923 + j 11.754 + 5.849 + j 0.467 = 14.772 + j 12.22 = /19.172/
I k9 = = = 1147 A
b) sistema ishlarini minimal rejim ( bir transformator ishlaganda S k. t. k. = 400 MVA)
Sistema qarshiligi
Xs = = = 1 Zc = j 1
K – 1 nuqta
ZE =Zc = j 1
I k1 = = = 2008 A
K – 2 nuqta
(bitta transformator ishlaydi)
Z E2= ZE1 + Z T1= j 1 + 0.24 + j 4.192 = 0.24 + j 4.192 = /5.198/
I k2 = = = 1201 A
K – 3 nuqta
Z E3= ZE2 + Z K1/2 = 0.24 + j 5.192 + 0.863 + j 0.65 = 1.103 + j 5.842 = /5.945/
I k3 = = = 1050 A
K – 4 nuqta
Z E4= ZE3 + Z L1= 1.0103 + j 5.842 + 1.81 + j 1.012 = 2.913 + j 6.854 = /7.447/
I k4 = = = 838 A
K – 5 nuqta
Z E5= ZE4 + Z T4= 2.913 + j 6.854 + 2.813 + j 16 = 5.726 + j 22.854 = /23.56/
I k5 = = = 24505 A
K – 6 nuqta
Z E6= ZE3 + Z T3= 1.103 + j 5.842 + 0.84 + j 7.45 = 1.943 + j 13.292 = /13.433/
I k6 = = = 1637 A
K – 7 (8) nuqta
Z E7 (8) = ZE6 + Z L4(5)= 1.943 + j 13.292 + j 0.758 = 9.043 + j 14.05 = /16.709/
I k7 (8) = = = 1316 A
K – 9 nuqta
Z E9 = ZE8 + Z L6= 9.43 + j 14.05 + 5.849 + j 0.467 = 14.892 + j 14.517 = /20.797/
I k9 = = = 1058 A
Ikki fazali qisqa tutashish tokini quyidagi formula buyicha aniqlaymiz:
I2kt = *I (3) k
Xisoblangan qisqa tutashish toklar natijasini A jadvalga yozamiz.
4-amaliy mashg’ulot
Kuchlanishi 35 kV li liniyalarni ximoyasini xisoblash
a) tok transformatorlarini tanlash sharti buyicha nominal toklarni aniqlaymiz
INTT INTR (2,1)
INOM t1(t2) = = = 52,5 A
Kuch transformatorini nominal toki asosida unga yaqin kattaroq bulgan nominal tokli tok transformatorini tanlaymiz. [1]. Uning qiymati IN birlamchi. TT = 75 A buladi.
SHunda transformatsiya koeffitsienti = = = 15
Xuddi shunday:
INOM t3 = = = 66 A
|
= = 15
|
INOM t4 = = = 26 A
|
= = 6
|
b) Elektr uzatish liniyasi (EUL) uchun:
INTT IRUX (2,2)
IRUXl1(l2) = 210 A , tok transformatori INTT = 300 A tanlaymiz.
Unda: = = 60
Xuddi shuningdek:
IRUX l3 = 175 A
|
= = 40
|
IRUX l4 (l5) = 80A
|
= = 20
|
IRUX l6 = 65 A
|
= = 15
|
Elektr tarmog‘ini xar bir elementi uchun releli himoya qurilmalarini xisoblashda tok transformatorlarini alohida tanlash mumkin.
Do'stlaringiz bilan baham: |