Controller is with Modbus RTU protocol, baud rate 9600, none even or odd, 8 data bit 
and 1 stop bit. Detailed table is as below. 
Function code
Register ad-
dress
Function
Data interpretation
03 
00000 
Indoor temperature
Temperature range
( 
0-50


Communication 
data=measured temperature*10
03 
00004 
Reserved

03/06 
00202 
Supply air fan On/off
0

Off, 1

On
03/06 
00203 
Exhaust air fan On/off
0

Off, 1

On
03/06 
00237 
Mode
0: Manual, 2: Time period; Default: Manual 
03/06 
00239 
Condition
0

on, 255

off 
Please note that function code 03 is loading position and 06 is writing position. 
Thermostat ID setting: 
When under ventilator off status, press 
and 
hold for 2
seconds, the controller enters the ID setting state. The screen displays "001" by default,
the default firstly changes the single digit, press the function key to select modify
digits, tens, and modify it by 
Or the range is 0-199. 
Commissioning
 
1.Check the connection after the installation is completed, and be sure to test it. 
2.Turn on the power supply and run the test according to the following table to check 
the working status of the blower and exhaust fan.
3. When an abnormality occurs in the test run, the wiring may be considered incorrect. In
order to prevent electric shock, please turn off the special circuit breaker immediately and
re-wire correctly. 


20
Use Considerations
After the energy recover ventilator is 
power on, the spark of the electrical con-
tact caus-es an explosion or fire. 
Do not insert your fingers or sticks into the 
fresh air inlet or the dirty air inlet. Due to 
the high speed rotation of the wind wheel, it 
is easy to cause injury 
Continuous operation in an abnormal state 
may cause malfunction, electric shock or 
fire.
Never modify, disassemble or repair it your-
self. Otherwise, it will cause the fan to burn
electric shock or fire. 
When cleaning the filter and the heat ex-
changer, the switch must be turned off to 
close the circuit breaker 
Do not install, move or reinstall yourself. If 
there is any improper, there will be acci-
dents such as falling, electric shock, fire, 
etc . 

Do not set the exhaust air inlet at a loca-
tion where it can absorb high temperature 
and high humidity air. Otherwise, it may 
cause adverse effects inside the unit
which may cause malfunction, electric 
leakage and fire. 
Do not place the burner near the ERV air 
outlet, otherwise, it may cause insufficient 
combustion of the burning appliance. 
When not used for a long time, please turn 
off the dedicated circuit breaker for safety. 
Do not use a flammable sprayer near the 
unit, as this may cause a fire. 
Clean the filter regularly, too much dust in 
the filter will cause hypoxia in the room. 
If set up the unit in ordinary ventilation 
during indoor heating in winter, it will 
cause condensation at the fresh air outlet 
of the unit, so it is forbidden to use ordi- 
nary ventilation in winter. 
ERV must be used according to the rated 
voltage., or it may cause fire or electric 
Do not wash the ERV unit with water, oth- 
erwise it may cause electric shock. 

The unit cannot be used for ventilation of
an open burning appliances (heating)
When using a gas or oil heater in the room,
special ventilation equipment must be used
To avoid injury, please pay special attention to the following when using: 
1. Do not insert your fingers and objects into the rotating part. 
2. Before using the tool to open the access panel, be sure to turn off the power. After 
the device is completely stopped, open the access panel to avoid injury.

警告


Heat Exchanger
Power must be isolated before installation and maintenance to avoid injury or electric
s
shock. Supply 
power cables, main circuit breaker and earth leakage protection, must comply with national regulations. 
Failure to observe could cause unit failure, electric shock or fire. 
Standard filtration is supplied with this unit and must be used. Dust and dirt can accumulate in the heat 
exchanger if filters are removed. (This can lead to failure or decreased performance). To ensure efficient 
operation, regular cleaning or replacement of filters is required. Filter maintenance frequency will de-
pend on working environment and unit running time. 

Download 2,74 Mb.

Do'stlaringiz bilan baham:
1   2   3   4   5   6   7




Ma'lumotlar bazasi mualliflik huquqi bilan himoyalangan ©hozir.org 2024
ma'muriyatiga murojaat qiling

kiriting | ro'yxatdan o'tish
    Bosh sahifa
юртда тантана
Боғда битган
Бугун юртда
Эшитганлар жилманглар
Эшитмадим деманглар
битган бодомлар
Yangiariq tumani
qitish marakazi
Raqamli texnologiyalar
ilishida muhokamadan
tasdiqqa tavsiya
tavsiya etilgan
iqtisodiyot kafedrasi
steiermarkischen landesregierung
asarlaringizni yuboring
o'zingizning asarlaringizni
Iltimos faqat
faqat o'zingizning
steierm rkischen
landesregierung fachabteilung
rkischen landesregierung
hamshira loyihasi
loyihasi mavsum
faolyatining oqibatlari
asosiy adabiyotlar
fakulteti ahborot
ahborot havfsizligi
havfsizligi kafedrasi
fanidan bo’yicha
fakulteti iqtisodiyot
boshqaruv fakulteti
chiqarishda boshqaruv
ishlab chiqarishda
iqtisodiyot fakultet
multiservis tarmoqlari
fanidan asosiy
Uzbek fanidan
mavzulari potok
asosidagi multiservis
'aliyyil a'ziym
billahil 'aliyyil
illaa billahil
quvvata illaa
falah' deganida
Kompyuter savodxonligi
bo’yicha mustaqil
'alal falah'
Hayya 'alal
'alas soloh
Hayya 'alas
mavsum boyicha


yuklab olish