IBC SECTION 424
Children’s Play Structures
*IBC Section 424.5; delete.
CHAPTER 5 – GENERAL BUILDING HEIGHTS AND AREAS
IBC SECTION 503
GENERAL BUILDING HEIGHT AND AREA LIMITATIONS
*IBC Section 503.1; add a second paragraph to read as follows:
An occupancy, including those on Occupied Roofs, shall not be located above the story or height set forth in Tables 504.3 and 504.4 except as modified hereafter. For non-separated mixed uses, in accordance with Section 508.3, no occupancy shall be located above the story or height of the most restrictive non-separated occupancy.
*IBC Section 503.1.4; added to read as follows:
503.1.4 Fire protection systems. Any existing fire extinguishing system or fire alarm system, whether installed voluntarily or as a requirement of any previous code, shall be maintained and kept operational as required in the Fire Code. Such systems shall not be removed unless permitted to be removed or reduced by this code and the Fire Code.
IBC SECTION 506
BUILDING AREA
*IBC Section 506.3.1; add a sentence to read as follows:
In order to be considered having access from the street or approved fire lane, if not in direct contact with a street or fire lane, a minimum 10 foot wide pathway meeting fire department access from the street or approved fire lane must be provided.
IBC SECTION 509
INCIDENTAL USES
*IBC Section 509.4.1; add two sentences to read as follows:
…Section 707 or a horizontal assembly constructed in accordance with 711, or both so as to completely separate adjacent occupancies.
*IBC Section 509.4.2; add two sentences to read as follows:
In order to qualify with this reduction, at least one sprinkler head must be installed in the incidental use area. Areas that are exempt to sprinkler head installation under a sprinkler standard will not qualify for the reduction permitted herein unless at least one sprinkler head is installed in the incidental use area.
CHAPTER 6 – TYPES OF CONSTRUCTION
IBC SECTION 602
CONSTRUCTION CLASSIFICATION
*IBC Table 602; amend footnote “d” to read as follows:
-
The fire-resistance rating of an exterior wall is determined based upon the fire separation distance of the exterior wall and the story in which the wall is located. When an upper floor projects closer to the property line than the floors below, and if Table 705.8 requires any percentage of protected openings for the exterior wall of that upper floor, then the underside of the projecting floor shall be a minimum of one-hour fire resistance rating.
IBC SECTION 603
COMBUSTIBLE MATERIAL IN TYPE I AND II CONSTRUCTION
*Section 603.1; change item 14 to read as follows:
-
Fire-retardant-treated wood used as blocking such as for handrails, millwork, cabinets and window and door frames.
CHAPTER 7 – FIRE AND SMOKE PROTECTION FEATURES
IBC SECTION 706
FIRE WALLS
*IBC Section 706.2; add exceptions to read as follows:
Exceptions:
1. When necessary to install a two- or three-hour fire wall of not more than two stories in height in an existing building, a fire-resistant wall of the same rating, as specified in Table 706.4, that encapsulates a structural column line shall be accepted.
2. When necessary to install a two- or three-hour fire wall of not more than two stories in height between an existing building and a new addition, a double fire wall, one on the existing building and one on the new building, both of the required fire rating, as specified in Table 706.4, shall be acceptable. Fire doors may be installed in one of the walls with a water curtain installed at the opening of the other wall.
IBC SECTION 712
VERTICAL OPENINGS
*IBC Section 712.1.9; change item 4 to read as follows:
712.1.9 Two-Story openings. In other than Groups I-2 and I-3, a vertical opening that is not used as one of the applications listed in this section shall be permitted if the opening complies with all of the items below:
1. Does not connect more than two adjacent stories.
2. Does not penetrate a horizontal assembly that separates fire area or smoke barriers that separate smoke compartments.
3. Is not concealed within the construction of a wall or a floor/ceiling assembly.
4. Is not open to a corridor in Groups H and I and R occupancies.
5. Is not open to a corridor on nonsprinklered floors in any occupancy.
6. Is separated from floor openings and air transfer openings serving other floors by construction conforming to required shaft enclosures.
7. Is limited to the same smoke compartment.
IBC SECTION 717
DUCTS AND AIR TRANSFER OPENINGS
*IBC Section 717.5.3.1; added to read as follows:
717.5.3.1 Installation requirements. Exhaust systems for Group B and R kitchen, clothes dryer, bathroom and toilet room exhausts shall comply with the following:
-
Kitchen systems, clothes dryer systems, and bathroom and toilet room systems may share the same shaft but not the same duct. When multiple ducts are in the same shaft, each system shall have its own fan providing continuous upward flow.
-
Dryer ducts shall have a cleanout located near the shaft penetration to permit cleaning of the 22” subduct. The subduct shall be considered in the calculation of allowable duct length reduction.
-
Kitchen ducts shall be provided with some method for preventing grease buildup and cleaning of the duct.
-
A secondary power source is required for the fan under both Section 909.11 and Mechanical Code Section 504.8.
-
See also Mechanical Code Section 504.8.
Do'stlaringiz bilan baham: |