Should evaluate the reactive power capability of the PV plant and should check whether PV plant is providing sufficient reactive support according to grid code requirements at the interconnection point.
Vary the PU Voltage at PCC to determine the reactive power required to meet the grid code requirements and identify if additional compensation is required to achieve this
Poor power factor-increases line losses & makes voltage regulation more difficult.
Voltage-regulating mode provide power factor correction.
CEA GUIDELINES:Generating units located near load center has allowed power factor of LSS plant range is 0.85 lagging to 0.95 leading & Generating units located far from the load center has Allowed power factor range of 0.9 lagging to 0.95 leading https://www.linkedin.com/pulse/grid-integration-issues-solar-pv-plant-devakumar-a