Equipment: Part 3
383
Figure 11.15
Rooftop AHU. (
Courtesy of Mammoth.
)
condenser and fan; a supply fan; air filter; and an economy-cycle out-
side-air control system with return, relief, and outside air dampers.
Unit arrangement may be single-zone or multizone. If the dampers at
the unit are removed, multizone units may be used as double-duct
systems. Single-zone units may be used for VAV, although airflow mod-
ulation with DX compressor / coil control can be a challenge. A typical
rooftop unit is shown in Fig. 11.15. The unit is mounted on a prefab-
ricated curb, with all roof penetrations inside the curb. All controls
are included, with only zone thermostats to be field-installed.