Chapter Nine
Higher flow rates decrease the film resistance but lead to higher air
and water pressure drops. Compromise is therefore necessary. One
factor in the airflow rate selection is that the condensed water on the
surface of the coil tends to carry over into the airstream at high ve-
locities. It is considered good practice to select cooling-coil air velocities
in the range of 400 to 600 ft / min and water velocities in the range of
3 to 6 ft / s.
The use of
counterflow
or
parallel-flow
fluid paths has a considerable
effect on coil performance. The two terms are illustrated in Fig. 9.24.
In counterflow, the entering (coldest) water contacts the leaving
(coldest) air, while leaving water contacts entering air. Thus the tem-
perature difference between the two streams is fairly uniform
throughout the coil. In parallel flow, the opposite effect occurs: The
coldest water contacts the warmest air, and vice versa. Figure 9.25
shows the temperature relationships graphically. Counterflow is much
more effective than parallel flow. The total heat transferred in the
system is a function of the coil surface area, the heat transfer factor
k
, and the temperature difference. Because the temperature difference
varies throughout the coil, it is described, for calculation purposes, by
a single number called the
log mean temperature difference,
denoted
by MED. So MED is determined by
GTD

LTD
MED

(9.2)
ln (GTD / LTD)
where GTD

greatest temperature difference, air to water
LTD

least temperature difference, air to water
ln

natural logarithm (base
e
)
(Sometimes MED is referred to as LMTD in the literature.)
Referring again to Fig. 9.24, for the counterflow arrangement,
GTD

78

55

23

F, LTD

58

45

13

F, and then MED

17.5

F. For parallel flow, GTD

78

45

33

F, LTD

58

55

3

F, and MED

12.6

F. This means that coil capacity would be re-
duced by about one-third if it were piped in parallel flow rather than
counterflow, all else being unchanged. In some cases (e.g., when the
leaving water temperature needs to be greater than the leaving air
temperature), parallel flow will not work at all.

Download 4,24 Mb.

Do'stlaringiz bilan baham:
1   ...   305   306   307   308   309   310   311   312   ...   581




Ma'lumotlar bazasi mualliflik huquqi bilan himoyalangan ©hozir.org 2025
ma'muriyatiga murojaat qiling

kiriting | ro'yxatdan o'tish
    Bosh sahifa
юртда тантана
Боғда битган
Бугун юртда
Эшитганлар жилманглар
Эшитмадим деманглар
битган бодомлар
Yangiariq tumani
qitish marakazi
Raqamli texnologiyalar
ilishida muhokamadan
tasdiqqa tavsiya
tavsiya etilgan
iqtisodiyot kafedrasi
steiermarkischen landesregierung
asarlaringizni yuboring
o'zingizning asarlaringizni
Iltimos faqat
faqat o'zingizning
steierm rkischen
landesregierung fachabteilung
rkischen landesregierung
hamshira loyihasi
loyihasi mavsum
faolyatining oqibatlari
asosiy adabiyotlar
fakulteti ahborot
ahborot havfsizligi
havfsizligi kafedrasi
fanidan bo’yicha
fakulteti iqtisodiyot
boshqaruv fakulteti
chiqarishda boshqaruv
ishlab chiqarishda
iqtisodiyot fakultet
multiservis tarmoqlari
fanidan asosiy
Uzbek fanidan
mavzulari potok
asosidagi multiservis
'aliyyil a'ziym
billahil 'aliyyil
illaa billahil
quvvata illaa
falah' deganida
Kompyuter savodxonligi
bo’yicha mustaqil
'alal falah'
Hayya 'alal
'alas soloh
Hayya 'alas
mavsum boyicha


yuklab olish