Power Status Message
Description
Voltage on Multiple
The Trex unit has detected voltage on more than one terminal.
This may be due to the following:
•
The AC adapter is attached to the Trex unit and is charging
the power module. Disconnect the AC adapter from the Trex
unit.
•
Noise is detected on the network.
•
Two lead sets are connected to two different fieldbus
segments or loops. This is not recommended.
Communication Status
Description
No Communication
The Trex unit has not detected any HART or fieldbus
communication.
Fieldbus Detected
The Trex unit has detected FOUNDATION fieldbus
communication.
HART Detected
Typical status when the Trex unit detects:
•
A HART device in burst mode.
•
Active HART communication from the digital control system.
•
A response to a polling message sent to the device.
This status may be sporadic and may alternate between HART
Detected and No Communication.
If unexpected communications are detected, remove the AC
adapter to isolate the Trex unit from noise.
3.8
Online menu or Device Dashboard
Depending on the device description (DD) for a device, the first online screen is an
Online
menu or a device dashboard menu. All devices show a Menu tab at the bottom of the
screen.
Online menu
An Online menu may display the following options, depending on the device type:
•
Device setup
•
Primary variable (PV)
•
Analog output (AO)
•
PV lower range value (LRV)
•
PV upper range value (URV)
Field Communicator application
User Guide
September 2021
60
User Guide
Dashboard menu
A device dashboard menu displays the same parameters as the
Online
menu, but they are
organized by tab, including:
•
Overview
- View a graphical representation of the process variable. Tap the
More
arrow on the bottom right side of the screen to access additional menu items.
Depending on the device description, the images under "Device" and
"Communications" may be selectable links.
•
Service Tools
- View and modify options for alerts, variables, and maintenance. For
FOUNDATION fieldbus devices, the
Service Tools
option lets you edit the device tag
and address, and set the IO block schedule and the link master device. You can also
access the blocks directly from the
Block List
option on the
Service Tools
screen.
•
Configure
- Configure the device parameters.
The options below vary based on the device description for the device.
User Guide
Field Communicator application
September 2021
User Guide
61
Do'stlaringiz bilan baham: |