Operational issues:
✔
The intermittent nature of the
wind and solar generation poses certain operational
challenges for the transmission grid, including ad-
ditional ramping and regulation requirements and
impacts on system stability. For example, due to the
steepness of the wind turbine power curve (as shown
in Figure 2), a wind farm creates signifi cant ramp-
ing needs as wind speed changes, with the wind
farm typically operating at either low output or high
output at any given time. At high wind speeds, the
turbine controls cut off the power generation to pre-
vent damage to the blades and the turbine-generator
assembly due to overspeed and possible tensional
oscillation. This power cutoff poses additional
operational challenges due to a very steep reduction
in generation levels.
Do'stlaringiz bilan baham: |