Chapter hvac engineering Fundamentals: Part 1 Introduction



Download 4,24 Mb.
Pdf ko'rish
bet66/581
Sana01.02.2022
Hajmi4,24 Mb.
#424428
1   ...   62   63   64   65   66   67   68   69   ...   581
Bog'liq
HVAC HANDBOOK

74
Chapter Three
a slope equal to the sensible / total (
S/T
) ratio (in this case
5

6
, or
0.833). In the figure this is line
RS.
Theoretically, the supply air point
may be anywhere on this line. In practice, there are limitations, as
discussed below.
2. On any chart the slope of the supply air process line may be
determined by assuming a TD and calculating the resulting

w.
In
this example, a TD of 20

F has been used, so that the supply point
S
is at 55

F. Then the design CFM will be
50,000 Btu / h
3
CFM


2315 ft / min
20

F

1.08
where 1.08 is the air factor for standard air. Using this CFM, we can
calculate the value of

w
:
10,000 Btu / h

w
0.0009 lbw / lba
3
2315 ft / min

60

0.075

1059
where 60

min / h
0.075

air density, lb / ft
3
(standard air)
1059

latent heat of vaporization of water at 60

F, Btu / lb
The

w
of 0.0009 subtracted from the room
w
of 0.0092 equals
0.0083, the needed
w
of the supply air at point
S
. Then, from the chart,
the supply air properties are 55

F db, 53.3

F wb,
h

22.2,
w

0.0083,
and RH

90 percent. By projection to the saturation line, the
appa-
ratus dew point
(ADP) is 51

F.
The figure of 90 percent RH presents a problem because it im-
plies a coil bypass factor of about 14 percent (see the coil discussion in
Chap. 9). A present-day cooling coil, even at four rows deep, will do
much better, with a bypass factor as low as 5 percent. It follows that
the design condition will not be obtained in practice and, if the supply
air temperature is controlled at 55

F, the resulting room condition will
be at a somewhat higher humidity than the design value. In this ex-
ample, the error is probably not serious, but the design is, in fact,
flawed. While the 20

F TD is not too far off, a TD of 15 or 16

F would
be unrealistic (unless reheat were used—a no-no in these energy-
conscious days except for humidity control).
The ADP of 51

F will require a supply water temperature of about
45

F. With a DX coil, the ADP will tend to be between 40 and 45

F
(see Fig. 3.12), which will pull the room humidity downward, increas-
ing the load due to dehumidification of outside air. It will also lower
the supply air temperature so that the TD will be 25

F or more. Then
the airflow rate should be 1850 ft
3
/ min. From experience this would
be expected to result in cold drafts and rapid two-position response
Design Procedures: Part 1
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.



Download 4,24 Mb.

Do'stlaringiz bilan baham:
1   ...   62   63   64   65   66   67   68   69   ...   581




Ma'lumotlar bazasi mualliflik huquqi bilan himoyalangan ©hozir.org 2024
ma'muriyatiga murojaat qiling

kiriting | ro'yxatdan o'tish
    Bosh sahifa
юртда тантана
Боғда битган
Бугун юртда
Эшитганлар жилманглар
Эшитмадим деманглар
битган бодомлар
Yangiariq tumani
qitish marakazi
Raqamli texnologiyalar
ilishida muhokamadan
tasdiqqa tavsiya
tavsiya etilgan
iqtisodiyot kafedrasi
steiermarkischen landesregierung
asarlaringizni yuboring
o'zingizning asarlaringizni
Iltimos faqat
faqat o'zingizning
steierm rkischen
landesregierung fachabteilung
rkischen landesregierung
hamshira loyihasi
loyihasi mavsum
faolyatining oqibatlari
asosiy adabiyotlar
fakulteti ahborot
ahborot havfsizligi
havfsizligi kafedrasi
fanidan bo’yicha
fakulteti iqtisodiyot
boshqaruv fakulteti
chiqarishda boshqaruv
ishlab chiqarishda
iqtisodiyot fakultet
multiservis tarmoqlari
fanidan asosiy
Uzbek fanidan
mavzulari potok
asosidagi multiservis
'aliyyil a'ziym
billahil 'aliyyil
illaa billahil
quvvata illaa
falah' deganida
Kompyuter savodxonligi
bo’yicha mustaqil
'alal falah'
Hayya 'alal
'alas soloh
Hayya 'alas
mavsum boyicha


yuklab olish