Equipment: Part 3
371
Figure 11.4
Zone reheat coil.
A single-zone unit may be used to control humidity in the room. The
unit is arranged as shown in Fig. 11.5. The cooling coil precedes the
heating coil, which is therefore in the reheat position. Humidity con-
trol always requires additional energy—as reheat or in other ways.
The cooling coil valve is controlled by either the space temperature or
the space humidity, whichever creates the greater demand. If humid-
ity controls, the temperature will tend to fall and the space thermostat
will control the heating coil valve to provide reheat. The humidifier is
used when required.