198
◾
Introduction to Industrial Automation
from the PLC. However, it should also be noted that the scanning time is directly dependent on
the speed of the microprocessor, while for a specific PLC, this time is dependent only on the size
of the program (number of instructions) and the type of these instructions, since different instruc-
tions demand a correspondingly different execution time. As an indication of the scanning speed
of a PLC, manufacturers usually provide the scanning time for a program that contains a set of
instructions of 1 KB of memory.
PLCs are not programmed according to an internationally standardized programming lan-
guage that is adopted by all manufacturers. Instead, there are various forms of programming
languages that vary from company to company under various names, even if they are similar
in their functionality. Also, there is a significant incompatibility between similar programming
languages developed by different manufacturers. The International Electrotechnical Commission
standard 61131 (IEC 61131-3), which was adopted in 1993, deals specifically with PLC program-
ming languages, and defines the most basic forms that fall into two categories: graphic languages
and text-based languages.
Despite the lack of an absolute standardization in the matter of scheduling, we can distinguish
three main programming languages, which are: the cascade ladder diagram language (ladder),
the instruction list language or Boolean (IL), and the language of logic elements or function
block diagram (FBD). The most popular of these is ladder language, since it is very similar to
the classic implementation of an automation circuit. This was also the reason for the adoption of
this language by almost all manufacturers in the early years of PLCs, because in this way it was
easier to spread the novel PLC technology and have it adapted by older engineers who were not
familiar with the programming. In Figure 6.4, the general format of the three programming lan-
guages is presented, where the specific program represents a conventional automation circuit for
the START-STOP with self-latch operation of a motor (see Section 3.1.1).
As mentioned above, the programming device for a PLC can be a PC or a specially designed
digital device. In the second case, the programming device or programmer is not just a simple
keyboard, but includes a liquid crystal display, a memory, a compiler, and various communica-
tion ports to communicate with the PLC or other peripheral devices. These units are necessary
in a programming device, since the programming is not performed directly in the PLC. For the
programming procedure, initially the program is developed in the programming device and after-
wards it is translated into a machine language that is stored initially in the programmer’s memory
and then transferred to the PLC’s memory, provided that there is a communication link between
the programmer and the PLC. From the programmer, it is usually feasible to monitor the opera-
tion of the PLC in order to detect the status of the PLC’s internal elements and to perform various
diagnostic tests.
I1
Q1
I2
Q1
ANOT I1
AND I2
OR
Q1
OUT Q1
Ladder diagram
Instruction list
Logic diagram
AND
OR
Q1
I2
I1