Introduction to Industrial Automation


   Starting the Operation of a PLC and Fault Detection



Download 43,9 Mb.
Pdf ko'rish
bet275/440
Sana01.01.2022
Hajmi43,9 Mb.
#294756
1   ...   271   272   273   274   275   276   277   278   ...   440
Bog'liq
Introduction to Industrial Automation by Stamatios Manesis, George

6.10.10   Starting the Operation of a PLC and Fault Detection

The procedure of the first-time operation of a PLC should contain careful steps in order to exclude 

destructive damage of the I/O modules, CPU, power supply, or any other equipment involved. 

Before putting a PLC into operation for the first time, the entire installation should be examined 

and verified in accordance with the manufacturer’s specifications and the national or international 

regulations. Additionally, the good grounding of the system should be specifically checked. Before 

powering up the PLC, the following actions are needed:

  1. Ensure that the supply voltage for the PLC corresponds to the one needed from the PLC. 

Many PLCs are capable of receiving more than one electrical supply voltage, such as 230 V 

AC and 110 V AC. The selection is made either with a special switch or with a jumper in the 

appropriate position. In many cases, it is quite common that the PLC is set for an AC voltage 

of 110 V AC and, in the end, supplied with 230 V AC with catastrophic results.

  2. Check that all the power and communication cables are correctly positioned in their respec-

tive slots. The communication connectors fitted with locking screws should be carefully 

installed in their correct positions.

  3. Examine whether all the I/O modules are correctly positioned on the mounting base for the 

case of a modular PLC, and that there is a communication “bridge” between each one and 

the next one.

  4. Put the operational mode switch of the PLC in the STOP position.

  5. If the electric installation includes a general emergency switch (e.g., an emergency STOP 

button), make sure it is OFF or in the open contact position.

  6. Ensure that all the output devices are not powered.

Once the previous steps are completed, supply power to the PLC and check that the status of 

all the LEDs on the central processing unit are as the manufacturer of the PLC specifies them. Also 

check that the status of all the input devices, ON or OFF, are in conformity with the logic of the 

automation program. This simply means that some input devices are normally closed contacts, so 

that the corresponding LEDs of the digital inputs are lighted (ON state). Then, the input devices 

that are in the normally open contact state should be checked by causing a manual activation of 

each of them. For example, in the case of a button, it should be simply pressed, or in case of a 

photocell on a conveyor belt, an object should be interfered to check the corresponding activation. 

Whenever an input device of this category (e.g., a NO contact) is activated, the corresponding LED 

of the digital input of the PLC should also be activated. In this way, it is ensured that the input 

devices are functioning properly, if the wiring of the input devices was implemented correctly, and 

whether the input device and input address match the one contained in the automation program. 

Subsequently, the PLC is set to the run mode (RUN) and the outputs are checked so they behave 




262

 



  Introduction to Industrial Automation

according to the logic of the automation program. This test can be based on the indicating LEDs 

of the digital outputs, the state of the power relays provided, or the power supply of the loads that 

were interrupted according to action 6, above. In order to control the correctness of the automation 

program, it does not need to operate large loads (such as large motors) at the stage of the first test 

of the PLC.

If the above check reveals an operating problem in either the general operation of the PLC, or 

in one or more inputs or outputs, then the debugging process of either the program or the hard-

ware is followed. This process, in order to have a quick and effective outcome, should be systematic 

and include the following three basic steps:

 



The isolation of the operational problem from other possible ones

 



The identification of the operational symptom or the equipment fault

 



The careful fault correction and restoration

If the problem concerns the actual operation of the PLC and the CPU, then the indicating 

LEDs should be checked in order to diagnose the operating status of the PLC and follow the 

manufacturer’s debugging instructions. The CPU and the AC power adapter may have some or all 

of the following indication LEDs.

 



DC or AC POWER ON

 



TEST MODE (A PLC can be in STOP, RUN, TEST, programming mode, etc.)

 



PROCESSOR FAULT

 



MEMORY FAULT

 



I/O FAULT

 



LOW BATTERY FAULT

If the problem involves a digital input or output, then some basic actions for the debugging 

process are as follows:

  1. Suppose a digital input device (e.g., a limit switch) is switched on (the contact of the 

switch is closed) and causes a digital output to be activated. If this is not the case then if, 

with an activated input device, the indicative LED of the digital input is activated, then 

the problem is due to the digital input module or possibly to the logic of the executed auto-

mation program. If, with an activated input device, the indicative LED does not light up, 

then the problem is due either to the input device or to its wiring. In this case, measuring 

the voltage at the corresponding digital input of the PLC, as shown in Figure 6.55, will 

help derive a final conclusion.

  2. If the device assumed that a digital output of a PLC is enabled, but the corresponding output 

device connected to it is not activated, and the digital output LED does not light up, then 

the problem exists in the digital output module. If the digital output indicator LED lights 

up but the output device is not activated, then the problem exists either in the wiring of the 

output device or on the device itself.

In both cases, measuring the voltage at the digital output of the PLC, as shown in Figure 6.56, will 

help to accurately locate the fault.




Basic Operating Principles of PLCs 



 



263

Special attention should be provided when the output of the PLC is utilizing a triac as a switching 

element. In this case, the triac has a high internal resistance when not conducting (about 1 M

Ω

), so the 



insertion of a voltmeter, which also has a high internal resistance (about 6–10 M

Ω

), results in a volt-



age divider generated when the digital output has no load. In this case, the indication of the voltmeter 

may be close to the nominal voltage of the digital output even when the triac is OFF. For the voltmeter 

indication to be correct, a 10 K

Ω

 resistor should be connected in parallel to the instrument’s terminals, 



as presented in Figure 6.57. Then the total resistance of the instrument will be much smaller than that 

of the triac, and the indication will be almost zero for a non-conducting triac.

PLC

INPUTS


OUTPUTS

0 V


C

1

C



2

C

3



+24 V DC 

0 V


 

+24 V DC 

Q 0.0

I 1.0


I 1.4

S

1



S

3

Q 0.2 Q 0.4



S

2

I 1.2



PLC

INPUTS


OUTPUTS

 

Q 0.0



I 1.0

I 1.4


Q 0.2 Q 0.4

I 1.2


V

PLC


Inputs

Outputs


Q 0.0

I 1.0


I 1.4

Q 0.2 Q 0.4

I 1.2

V


Download 43,9 Mb.

Do'stlaringiz bilan baham:
1   ...   271   272   273   274   275   276   277   278   ...   440




Ma'lumotlar bazasi mualliflik huquqi bilan himoyalangan ©hozir.org 2024
ma'muriyatiga murojaat qiling

kiriting | ro'yxatdan o'tish
    Bosh sahifa
юртда тантана
Боғда битган
Бугун юртда
Эшитганлар жилманглар
Эшитмадим деманглар
битган бодомлар
Yangiariq tumani
qitish marakazi
Raqamli texnologiyalar
ilishida muhokamadan
tasdiqqa tavsiya
tavsiya etilgan
iqtisodiyot kafedrasi
steiermarkischen landesregierung
asarlaringizni yuboring
o'zingizning asarlaringizni
Iltimos faqat
faqat o'zingizning
steierm rkischen
landesregierung fachabteilung
rkischen landesregierung
hamshira loyihasi
loyihasi mavsum
faolyatining oqibatlari
asosiy adabiyotlar
fakulteti ahborot
ahborot havfsizligi
havfsizligi kafedrasi
fanidan bo’yicha
fakulteti iqtisodiyot
boshqaruv fakulteti
chiqarishda boshqaruv
ishlab chiqarishda
iqtisodiyot fakultet
multiservis tarmoqlari
fanidan asosiy
Uzbek fanidan
mavzulari potok
asosidagi multiservis
'aliyyil a'ziym
billahil 'aliyyil
illaa billahil
quvvata illaa
falah' deganida
Kompyuter savodxonligi
bo’yicha mustaqil
'alal falah'
Hayya 'alal
'alas soloh
Hayya 'alas
mavsum boyicha


yuklab olish