170
Chapter Six
Figure 6.11
Basic chart for flow rate and velocity of steam in schedule 40 pipe. (
SOURCE
:
Copyright 2001, American Society of Heating, Refrigerating and Air Conditioning En-
gineers, Inc., www.ashrae.org. Reprinted by permission from ASHRAE Handbook,
2001
Fundamentals,
Chap. 35, Fig. 10.)
the out-and-back system will have the lowest first cost but the highest
pumping cost. The loop system will have an intermediate first cost
and the lowest pumping cost. The reverse-return system will have the
highest first cost and an intermediate to low pumping cost. The loop
system is preferable but only if the geometry is suitable.
Design Procedures: Part 4
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
Any use is subject to the Terms of Use as given at the website.