Pinch decomposition
other pinches, termed utility pinches, that cause further problem decomposition. Problem decomposition can be exploited in algorithms for automatic heat exchanger network synthesis.
3.17.2 THE PROBLEM TABLE METHOD
The problem table is a numerical method for determining the pinch temperatures and the minimum utility requirements, introduced by Linnhoff and Flower (1978). It eliminates the sketching of composite curves, which can be useful if the problem is being solved manually. It is not widely used in industrial practice any more, due to the wide availability of computer tools for pinch analysis (see Section 3.17.7).
The procedure is as follows:
Convert the actual stream temperatures Tact into interval temperatures Tint by subtracting half the minimum temperature difference from the hot stream temperatures, and by adding half to the cold stream temperatures:
ΔTmin cold streams Tint ¼Tact þ 2
The use of the interval temperature rather than the actual temperatures allows the minimum temperature difference to be taken into account. ΔTmin ¼ 10°C for the problem being considered; see Table 3.3.
Note any duplicated interval temperatures. These are bracketed in Table 3.3.
Rank the interval temperatures in order of magnitude, showing the duplicated temperatures only once in the order; see Table 3.4.
Carry out a heat balance for the streams falling within each temperature interval:
Note: Duplicated temperatures are omitted. The interval ΔT and streams in the intervals are included as they are needed for Table 3.5.
where
ΔHn ¼ net heat required in the nth interval
ΣCPc ¼ sum of the heat capacities of all the cold streams in the interval
ΣCPh ¼ sum of the heat capacities of all the hot streams in the interval
ΔTn ¼ interval temperature difference ¼ (Tn1 Tn)
See Table 3.5.
“Cascade” the heat surplus from one interval to the next down the column of interval temperatures; Figure 3.24a.
Cascading the heat from one interval to the next implies that the temperature difference is such that the heat can be transferred between the hot and cold streams. The presence of a negative value
*Note: The streams in each interval are given in Table 3.4.
122 CHAPTER 3 FUNDAMENTALSOFENERGYBALANCES
(a) (b)
From (B) pinch occurs at interval temperature 85C.
FIGURE 3.24
Heat cascade
in the column indicates that the temperature gradient is in the wrong direction and that the exchange is not thermodynamically possible.
This difficulty can be overcome if heat is introduced into the top of the cascade:
6. Introduce just enough heat to the top of the cascade to eliminate all the negative values; see Figure 3.24b.
Comparing the composite curve, Figure 3.22, with Figure 3.24b shows that the heat introduced to the cascade is the minimum hot utility requirement and the heat removed at the bottom is the minimum cold utility required. The pinch occurs in Figure 3.24b where the heat flow in the cascade is zero. This is as would be expected from the rule that for minimum utility requirements no heat flows across the pinch. In Figure 3.24b the pinch is at an interval temperature of 85°C, corresponding to a cold stream temperature of 80°C and a hot stream temperature of 90°C, as was found using the composite curves.
It is not necessary to draw up a separate cascade diagram. This was done in Figure 3.24 to illustrate the principle. The cascaded values can be added to the problem table as two additional columns; see Example 3.16.