2.Timeout Loading:
After removal of the input and the closure of the flow control valve,
loading is paused for the time set with the Clear/Reconnect timer.
However the operator is given the option of restarting the load
once the input is restored to an active state.
3.Pause:
Loading is paused indefinitely by the removal of the input, and the
flow control valve is closed. Loading can be resumed or
discontinued on reconnection of the input/permissive.
4.Terminate:
The load is terminated as soon as the input is disconnected, and
cannot be restarted without going through the initial authorization
process.